Install the RS485-Ethernet converter

This article describes the on-site installation of the RS485-Ethernet converter. This equipment does not need to be registered on the Climkit platform, unlike other equipment.

Installation of the RS485-Ethernet Converter

  1. Connect the electrical power cable from the 24V AC/DC power supply to ports 1 and 2 of the device according to the correspondence table below.
  2. Connect the RS485 bus of the Modbus meters to ports 5, 6, and 7 of the device according to the correspondence table below.
  3. Connect the Ethernet/RJ45 port (LAN) to the router.

    Port

    Description

    1

    24 VDC +

    2

    24 VDC -

    5

    RS485 B (-)

    6

    RS485 A (+)

    7

    RS485 GND

    RJ45

    Ethernet/RJ45

  4. The device starts up in a few seconds and the Power and NET LEDs remain lit.