Install the RS485-Ethernet converter

This article describes the on-site installation of the RS485-Ethernet converter. This equipment does not need to be declared on the Climkit Platform, unlike other equipment.

Installation of the RS485-Ethernet converter

  1. Connect the electrical power cable from the AC/DC 24V power supply to ports 1 and 2 of the device according to the correspondence table below.
  2. Connect the RS485 bus of the Modbus meters to ports 5, 6 and 7 of the device according to the correspondence table below.
  3. Connect the Ethernet/RJ45 (LAN) port to the router.

    Port

    Description

    1

    24 VDC +

    2

    24 VDC -

    5

    RS485 B (-)

    6

    RS485 A (+)

    7

    RS485 GND

    RJ45

    Ethernet/RJ45

  4. The device starts in a few seconds and the Power and NET LEDs remain lit.
A label is provided with the order ("Attention - metering system in service"). It must be visibly stuck on the electrical panel once the Technical setup validation of the Site has been carried out by Climkit.