Inepro PRO380 Meters and Various

Nicolas Vodoz Updated by Nicolas Vodoz

1. Meter Inepro PRO380

Modbus Addressing

  1. Navigate using the right button to "Pro-2".
  2. Press and hold the right button for 3 seconds to access the menu.
  3. Under "addr", press and hold the right button for 5 seconds to enter programming mode.
  4. Edit and confirm each digit by pressing both buttons for 3 seconds.
  5. Exit the menu by pressing and holding the left button for 3 seconds.
pro380_mode_1.png

CT Ratio (PRO380-CT only)

Warning: the operation below can only be performed once and cannot be modified after.
  1. Turn on the meter. For a few seconds, the message "SEt Ct" will be displayed followed by "Ct5 0005".
pro380_ratio.png
  1. Select the secondary current Ct5 (for CTs /5A) on the left side of the dial, then confirm by pressing both buttons for 3 seconds.
  2. On the right side of the dial, enter the primary current (e.g., 0300 for 300A CTs) and confirm each digit by pressing both buttons for 3 seconds. Note that this can only be done once. If an error occurs, the meter must be replaced.
  3. That's it! The CT ratio is saved.

Video example for CTs of 300/5A

2. Meter Orno OR-WE-516 and Polier MTR80LMOD

Modbus Addressing

It is not possible to change the primary Modbus address of this type of meter via the context menu.

The default address corresponds to the last 3 digits of the meter's serial number.

It is also possible to obtain the address through the meter's context menu. The meter below has address 73.

id_address_polier_meter.jpg

During commissioning, it is therefore necessary to record this number along with the location of the meter and enter them into the portal.

How Did We Do?

Meter Read Manually

Configuration of ABB charging station

Contact